Installation and maintenance by specialist technicians
Warranty and genuine spare parts
APPLICATION
Valve to avoid a fuel spill because of an excessive filling of the aerial tanks.
It is installed in the filling tank ho.e. This valve closes the liquid flow when the product level gets almost its capacity total, using a buoy and a Venturi jet system, causing some hose strokes and a flow reduction which means the supply must be cut.
The lower valve diameter is intended for the 2” discharge pipes.
It has included a special key for an easy installation.
OPERATION
This valve is designed to close the fuel pass when its level is around 203 mm from the tank capacity.
Then a small bypass valve will allow emptying the hose with a flow of 19 l/min until the liquid level gets 76 mm of the tank capacity. The bypass valve completely closes the fuel pass.